A model for the response time of aeration systems at WWTPs is proposed. It includes the delays caused by the air supply system (consisting of blowers, throttles and pipes), the rise time of the air bubbles and all control loops except the master DO controller. Beside a description of the required step-change experiments, different approaches for model calibration are given depending on the available data. Moreover, the parameters for the oxygen transfer and the response time of the aeration system model are not clearly identifiable. The model can be used for simulation studies which compare different types of controllers under changing loading and process conditions. The results from full-scale experiments at three different plants show that the response times of the aeration systems are in the range of 4-5 min. Taking all processes and time constants into account, some 30 min are needed to reach a new steady state after a step change of the airflow rate.