电容器
电容
电气工程
电压
局部放电
工程类
电力电缆
振荡(细胞信号)
功率(物理)
去耦电容器
高压
电子工程
材料科学
物理
电极
复合材料
生物
量子力学
遗传学
图层(电子)
作者
Guangya Zhu,Kai Zhou,Shilin Zhao,Yuan Li,Lu Lu
出处
期刊:IEEE Transactions on Power Delivery
[Institute of Electrical and Electronics Engineers]
日期:2019-10-28
卷期号:35 (4): 1678-1684
被引量:25
标识
DOI:10.1109/tpwrd.2019.2949843
摘要
This paper presents a novel oscillation wave test system (OWTS) to detect the partial discharge (PD) of mounting defects in power cable insulation. In the proposed system, a charging capacitor is added to the circuit topology based on the traditional OWTS. The charging capacitor is charged to the desired voltage by a high-voltage DC power source. After the charging process, the test cable sample is charged by the capacitor. The resonant circuit is formed by the charging capacitor, the test cable, and the resonant reactor to create an oscillating decay voltage. With this novel method, no space charge is injected into the cable insulation. The effect of the charging capacitance on the charging efficiency is calculated with the Multisim software. This paper describes the working principle and the assembly of a laboratory prototype for the PD detection of a 500 m cable circuit. The test results show the feasibility of the novel OWTS method.
科研通智能强力驱动
Strongly Powered by AbleSci AI