空调
气体压缩机
高效能源利用
冷却能力
性能系数
环境科学
单位(环理论)
索引(排版)
冷负荷
汽车工程
计算机科学
运营管理
工程类
电气工程
机械工程
数学
万维网
数学教育
制冷剂
作者
I Made Rasta,I Nyoman Suamir
出处
期刊:Journal of Advanced Research in Fluid Mechanics and Thermal Sciences
日期:2021-06-06
卷期号:83 (1): 118-139
被引量:2
标识
DOI:10.37934/arfmts.83.1.118139
摘要
This paper presents results of a study on split air conditioning (AC) performance of a city hotel in Bali, Indonesia. The study applied a practical global approach to appraising the performance of existing AC systems and their installation in a city hotel. The results obtained indicate that improper AC system selection and installation potentially reduces their energy performance which include COP (coefficient of performance), EER (energy efficiency ratio), and SEI (system efficiency index). The finding also shows that improper system selection and installation has damaged 54 unit compressors of 90 AC systems installed in a particular building within three years’ period. Overall number of compressors that have been damaged in three years can reach 76 units accounted for about 23.1% of the total AC systems installed in the hotel. It is also found a reduction on AC system cooling capacity.
科研通智能强力驱动
Strongly Powered by AbleSci AI