制冷剂
聚光镜(光学)
蒸发器
蒸汽压缩制冷
火用
制冷
微通道
热力学
材料科学
可用能
环境科学
核工程
工程类
气体压缩机
物理
光学
光源
作者
K. B. Prakash,Chidambaram Subramanian,M. Chandrasekaran,B. Kalidasan,A Amarkarthik,P Manojkumar,S Saravanakumar
标识
DOI:10.36909/jer.icmmm.15661
摘要
Vapour Compression Refrigeration (VCR) system with high COP, low input power consumption and minimal exergy losses are of great research hotspot. The current research focuses on analysis of exergy and performance of vapour compression refrigeration (VCR) cycle is in a real-world application. Experiments were carried out in the VCR system using round tube condenser and microchannel condenser along with different refrigerants R134a, and R1234yf. Temperatures were varied from +20°C to 5°C for the evaporator and 40°C to 50°C for the condenser. Among the two refrigerants, experimental results show that refrigerants operating in micro-channel condensers have COP of 6% and 4%greater higher with5% and 3% lower exergy loss compared to the round tube condenser for R134a and R1234yf respectively.R1234yf appears to be a better equivalent for R134a, according to the findings. The efficiency defect in the condenser is the greatest and least in the evaporator for the coolants examined.