Abstract Applying anticorrosion grease and aluminum‐clad steel (AC) wires to ACSR have been adopted as general methods to protect overhead transmission line conductors and/or wires from corrosion. However, in some cases those means have been found to be ineffective on some transmission lines passing through acid atmosphere in the vicinity of a factory exhausting acid smoke. The corrosion caused by acid atmosphere is characterized by a higher speed in its progress as is well known. As means against such acid corrosion, application of high‐purity aluminum, selective removal of intermetallic compound in aluminum, and plastic coating wires have been reported before, and each has both advantages and disadvantages. In a former report, we found that a new type of anticorrosion grease shows an excellent property against acid atmosphere as well as in a salty condition. Here we present a new type of anticorrosion technology of applying high‐corrosion‐resistance aluminum alloy or zinc coatings on each component wire of a conductor that we succeeded in developing through a serial study of anticorrosion methods on overhead transmission lines. © 2008 Wiley Periodicals, Inc. Electr Eng Jpn, 163(1): 41–47, 2008; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/eej.20365