A.S. Farag,M.H. Shewhdi,Xiaofeng Jin,C Wang,Tao Cheng,Xinzhou Dong,Sheng Gao,Jing Wang,Z Wang
标识
DOI:10.1016/s0378-7796(98)00157-6
摘要
Partial discharge (PD) is one of the major factors causing insulation damage of power transformers. This paper describes the development of on-line partial discharge monitoring system for transformers. The developed set can monitor up to four power transformers continuously. It uses various methods to reject interference and enhances monitoring sensitivity of PD effectively. The optical cable is applied to communicate between measurement system near transformers and the upper computer in the main control building. On-line calibration of partial discharge quantity is requisite for on-line detection or monitoring. This paper describes an on-line calibration method using pulse injection through tap of high voltage transformer bushings. It also discusses the influence of limit inductance and bushing capacitance, from tap of bushing to ground, in on-line calibration circuits. Influences of multi-grounding of the transformer tank for monitoring and calibration are also discussed. Simulation in laboratory and site test shows that the method is practically valid for on-line PD calibration of power transformers within permissible engineering error range under certain defined conditions. This system has been in operation steadily in 500 kV substations for more than 2 years.