计算
传热
因子(编程语言)
计算机科学
机械
材料科学
物理
算法
程序设计语言
作者
Yuyan Chen,Yingdong He,Nianping Li
出处
期刊:Buildings
[MDPI AG]
日期:2024-01-29
卷期号:14 (2): 366-366
被引量:1
标识
DOI:10.3390/buildings14020366
摘要
With the growing interest in radiant heating and cooling systems, driven by their improved efficiency and enhanced thermal comfort compared to air systems, there is an increasing need to develop a more accessible method for designers to understand the implications of radiation heat exchange between the human body and radiant panels. To address this, a novel angle factor calculation model, named the HNU Angle Factor Model, was developed, taking into account the spatial arrangement and geometric relationship between the human body and radiant panels. The angle factors obtained using the HNU Angle Factor Model exhibited good agreement with the results obtained with Fanger diagrams and the contour integral method, with average relative differences of 8.1% and 10.0% for 140 cases, respectively. Furthermore, placing a radiant panel on the floor while maintaining its fixed size can contribute to the creation of an even and efficient thermal environment for individuals in both seated and standing positions. By implementing the HNU Angle Factor Model in practical engineering applications, more effective utilization of radiant systems can be achieved, as it provides an evaluation of the heat transfer between the human body and radiant panels.
科研通智能强力驱动
Strongly Powered by AbleSci AI