Abstract The structural components inside power transformers are commonly made of high-density pressboard, due to its suitable mechanical and dielectric properties. Among these components are the spacers used in the windings of transformers, which are subjected to compressive loading during operation. The spacers are immersed in dielectric liquid and subjected to high temperatures and chemical reactions during the lifespan of the transformer, which result in the degradation of their dielectric and mechanical properties. The performance and reliability of the power transformer greatly depends on its mechanical integrity, so it is necessary to understand how ageing degrades the mechanical response of the high-density pressboard. In this study, spacers made of high-density pressboard and pieces of copper conductor were immersed in uninhibited paraffinic oil and aged at 150 °C for different periods of time, trying to realistically represent the process suffered by a power transformer during its whole lifespan. The evolution caused by the thermal ageing over some chemical parameters (acidity and moisture content) and dielectric properties (AC breakdown voltage, dielectric dissipation factor, resistivity and degree of polymerisation) of the oil and the pressboard was studied experimentally. Compressive mechanical tests were performed on samples of the aged high-density pressboard, and the compressive stiffness during the ageing process was related with other chemical and dielectric parameters.
科研通智能强力驱动
Strongly Powered by AbleSci AI