Christof Sumereder,T. Weiers
出处
期刊:IEEE Transactions on Energy Conversion
[Institute of Electrical and Electronics Engineers]
日期:2008-02-21
卷期号:23 (1): 9-14
被引量:24
标识
DOI:10.1109/tec.2006.888037
摘要
This study aims to gain insight into the consequences of local defects in stator winding insulation; therefore, optical (microscopic) inspections and voltage-endurance tests have been carried out on in-service aged generator bars. In this context, generator bars with mica-bitumen insulations and generator bars with mica-epoxy insulations were investigated. The mica-bitumen insulations had been in service for 43 years in a 12 kV hydro-generator. The generator bars with mica-epoxy insulation had been dismantled from two identically constructed 10.5-kV generators after 35 and 36 years of service. The time to breakdown values obtained from the voltage-endurance tests were evaluated using a Weibull distribution. Apart from the scale parameter, Weibull exponent of this distribution allowed for the identification of early failures. The voltage-endurance tests carried out on replacement bars for these generators did not yield any early failures; such failures, however, were detected on both types of the in-service aged insulations. In particular, these occurred at high levels of electric stress and at delaminations between the copper conductor and the groundwall insulation. It is concluded that the interpretation of the measured time to breakdown values and their scatter depends on the level of electric stress.
科研通智能强力驱动
Strongly Powered by AbleSci AI