Yong Han,Boon Long Lau,Gongyue Tang,Haoran Chen,Xiaowu Zhang
出处
期刊:IEEE Transactions on Components, Packaging and Manufacturing Technology
[Institute of Electrical and Electronics Engineers]
日期:2019-08-08
卷期号:10 (2): 255-262
被引量:16
标识
DOI:10.1109/tcpmt.2019.2933864
摘要
With the rapid growth of information technology (IT), the requirement of higher computing performance results in a much higher power density in data center server. A Si microfluid cooler with jet-slot array has been developed for direct liquid cooling of a server processor in a data center to handle increased heating power and maintain stable and uniform thermal performance. To mitigate the energy cost of the cooling system, the developed liquid cooling solution can enable aggressive heat removal capability with a low power consumption requirement. A stacked Si cooler of three plates and four different layer structures has been designed, fabricated, and tested. The novel heat sink includes jet-slot array, drain-slot array, and multiple pin fins. By overcoming the negative cross-flow effect, a high heat transfer rate has been obtained, covering the whole cooling area. With a volume flow rate of 0.5 L/min, 150-W chip heating power can be dissipated while maintaining the maximum chip temperature rise of ~15 °C. A chip temperature variation of 5% has been realized, suggesting much desirable cooling uniformity for the whole chip. With the Si structure, this liquid cooling solution can be directly implemented onto the chip, and the thermal path can be sharply shortened, which enable a decreased thermal resistance between the cold plate and the heat source. Great agreement has been obtained between the experimental results and the simulation results. The developed direct liquid solution with Si cooler shows guarantee to enable the potential capability of future advanced server processors.
科研通智能强力驱动
Strongly Powered by AbleSci AI