期刊:IEEE Transactions on Power Electronics [Institute of Electrical and Electronics Engineers] 日期:2022-04-22卷期号:37 (10): 11475-11480被引量:29
标识
DOI:10.1109/tpel.2022.3168902
摘要
This letter analyzes the impact of hybrid voltage- and power-based synchronization control on the transient stability of grid-forming (GFM) inverters. It is found that the added voltage-based synchronization loop exploits the phase angle difference to resist frequency deviation, whose function is similar to the damper winding of synchronous generators. By resembling the large-signal model of such hybrid synchronization control (HSC) to the power-angle swing equation, it is proved that the HSC brings higher damping to the system and thus, enhances the transient stability of GFM inverters. Further, a comparative study of two active power controllers, i.e., the droop controller with a low-pass filter and the proportional-integral (PI) controller, is given. It is revealed that the HSC with the droop controller equivalently decreases the active power reference, which leads to better transient stability behavior than that of using the PI controller. The theoretical findings are corroborated by experimental tests.